Did you know Fire Doors must be inspected annually?

Did you know Fire Doors must be inspected annually?

 

In the United States, people continue to lose their lives in the very settings where they work and often the significant contributing factor are doors. Fire-rated doors are an integral part of a building’s overall fire protection. A properly operating fire door is a key component to stop the spread of deadly fire, smoke, and toxic fumes and gases. Fire doors that are used on a day-to-day basis increase the likelihood of a fire or smoke door not being in optimal condition to protect occupants in the event of a fire is quite high.

Fire doors are very well regulated throughout design, specification and installation of rated openings, including the language of the Life Safety Code, NFPA 80 and the International Building Code. But once a facility has received a certificate of occupancy, the Building Code is closed, and ceases to have effect, as the Fire Code is now in effect for operation and maintenance of the facility. The Life Safety Code now contains language requiring post-occupancy inspections of swinging fire doors and doors in the means of egress.

 

Fire doors and door hardware are subject to failure due to the constant usage they take in high traffic areas. Constant usage can lead to misalignment of the door which could potentially lead to failure of the door to close in the event of a fire. Other common non-compliant issues are holes or openings in the fire door assembly, improper gaps, missing labels, failure of latching hardware to operate, missing screws, door coordinator operates improperly, non-working self-closing devices, missing gasketing, improper kick plates (protective plates) sizes, improper field modifications, and numerous other problems.

 

Top Ten Fire Deficiencies from the Door Security and Safety Foundation


The following items are the most commonly observed deficiencies found on swinging fire doors with builders hardware:

 

1. Painted or missing fire door labels
2. Poor clearance dimensions around the perimeter of the door in the closed position
3. Kick down door holders
4. Auxiliary hardware items that interfere with the intended function of the door barrel bolts and dead bolts, etc.
5. Fire doors blocked to stay in the open position
6. Area surrounding the fire door assembly blocked by furniture, equipment and/or boxes
7. Broken, defective or missing hardware items (latch bolts and/or strike plated, closer arms, cover plates, etc.)
8. Fire exit hardware installed on doors that are not labeled for use with fire exit hardware
9. Missing or incorrect fasteners
10. Bottom flush bolts that do not project into the strike

 

The National Fire Protection Association (NFPA), The International Code Council (ICC), and The Joint Commission all require the inspection of Fire Doors. The two primary NFPA Codes that have requirements for the maintenance and inspection of fire doors are NFPA 101®, Life Safety Code®, and NFPA 80, Standard for Fire Doors and Other Protective Opening Protectives®.